phone/data cable Add outlets to eliminate (unsafe) cables on floor in room 022. $500 <br />mgmnt <br />plumbing fixtures Room 014 clean electronic sensors at wash basin. Works only intermittently. $375 <br />plumbing fixtures Room 013 replace faucet at sink $313 <br />interior distribution Room 030 S.E. comer-rewire a receptacle wired in PVC L.T. flex. Replace $313 <br /> flex with emt conduit and new wiring. <br />.phone/data cable 2nd floor meth room -Secure coax cables laying across trusses. $250 <br />mgmnt <br />general lighting Room 3/4 (combined room) provide occupancy sensor for lighting control $250 <br />interior distribution Room 030 exterior wall in the generator cage: provide a cover to an LB $63 <br /> condulet. <br />interior distribution Room 030 N.W. bay o.h. door -provide knock out seals in the j-box above $63 <br /> the door on teh wall & secure the conduit stub feeding the control station on <br /> the north side of the door. <br />interior distribution Room 030 Replace the broken strap that secures the 11/4" conduit above the $63 <br /> transfer switch on the west wall adjacent to the generator <br /> Service Systems $54,813 <br />1 <br />1 <br />1 <br />1 <br />1 <br />1 <br />0 <br />0 <br />0 <br />Totals For - Ezisting Deficiencies (requiring correction: at time of audit) $190,519 <br />PR'Maintenance -Roosevelt vate Printed 18-Feb-o2 ~_6 <br />